1250A separable innercone connector IC 1250A size 3

IC1250A 140 x 105
Technical data:
Dimensions and scope of delivery
completely according to
EN 50181
Max. system voltage 42 kV
Nominal current 1250 A
Impulse (BIL) 200 kV
Short-time withstand current 0,5 s / 63 kA
Rated impulse current 150 kA
AC withstand 93,6 kV (5 min)
Thermal cycles and AC withstand 52 kV
DC voltage test (15 min) 125 kV
Partial discharge test < 10 pC at 42 kV
Meets the requirements of HD 629.1 & 60502-4
Application range Main insulation diameter
Max. cross-section 630 mm 51 mm
Type
1250A separable innercone connector IC 1250A size 3

Please select, in the table above, for which product variation(s) you would like to receive more information.
If you do not select a product variation, then we will contact you to discuss your requirements.